The PCD200 series are dual-input, field-programmable digital panel meters that accept two common process monitoring inputs, including 4-20mA and voltage signals, and provide a localized display of sensor data. The customizable process display and advanced math functions make it easy to get specific, actionable data in real time.
Buy This Online Now!
The PCD200 series are 1/8 DIN digital panel meters that accept two inputs of either a process current (4-20 mA) or process voltage (0-5V, 1-5V, ±10V). It displays these signals on a dual line, 6-digit process display that is available with an optional Sunbright® sunlight readable LEDs. The meter can be customized such that these two inputs are displayed in a variety of ways, including both at the same time with tags or the result of math functions performed on one or both of the inputs. The PCD200 process display panel meter features CE marking, a NEMA 4X front, and AC or DC power options. They can be equipped with up to four internal relays, a 4-20 mA analog output, and Modbus® serial communications. PCD200 panelmeters can be programmed via the front panel pushbuttons or the included PC-based software.
General | |
---|---|
Display | Upper display: 0.60: (15mm) high, lower display: 0.46” (12 mm) high, 6 digits each, red LEDs |
Front panel | NEMA 4X, IP65 |
Programming methods | Four front panel buttons, digit inputs, PC with MeterView software, Modbus registers, or cloning using Copy function |
Power options | 85-265 VAC, 50/60 Hz; 90-265 VDC, 20 W max; optional model with 12-24 VDC ±10%, 15 W max |
Required fuse | UL recognized, 5 A max, slow-blow; up to 6 meters may share one 5 A fuse |
Isolated transmitter power supply | Terminals P+ & P-: 24 VDC ± 10%. Internally selectable jumper for 24, 10, or 5 VDC supply. 85-265 VAC models rated @ 200 mA max, 12-24 VDC powered models rated @ 100 mA max, @ 50 mA max for 5 or 10 VDC supply. |
Isolation | 4 kV input/output-to-power line; 500 V input-to-output or output or output-to-P+ supply |
Temperature range | Operating: -40° to 65°C Storage: -40° to 85°C |
Relative humidity | 0 to 90% non-condensing |
Connections | Removable screw terminal blocks accept 12 to 22 AWG, RJ45 for external relays, digital I/O, and serial communication adapters |
Enclosure | 1/8 DIN, high impact plastic, UL 94V-0, color: black |
Mounting | 1/8 DIN panel cutout required: 3.622” x 1.772” |
Tightening torque | Screw terminal connectors: 5 lb-in (0.56 Nm) |
Weight | 269 grams (9.5 oz) |
USB connection | Compatibility: USB 2.0 Standard; compliant connector type: Micro-B receptacle; cable: USB A male to Micro-B cable; power: USB port |
Dual process input | |
---|---|
Inputs | Two non-isolated inputs, separately field selectable: 0-20 mA, 4-20 mA, 10 V (0-5, 1-5, 0-10 V), Modbus PV (Slave) |
Accuracy | ±0.03% of calibrated span ±1 count, square root & programmable exponent accuracy range: 10-100% of calibrated span |
Temperature drift | 0 to 65°C ambient: 0.005% of calibrated span/°C max -40 to 0°C ambient: 0.01% of calibrated span/°C max |
Signal input conditioning | linear, square root, programmable exponent, or round horizontal tank volume calculation |
Calibration range | 4-20 mA: minimum span input 1 & input 2: 0.15 mA ±10 V: minimum span input 1 & 2: 0.10 V |
Input impedance | Voltage ranges: >500 kΩ Current ranges: 50-100 Ω, varies with resettable fuse impedance |
Input overload | current input protected by resettable fuse, 30 VDC max |
Relays | |
---|---|
Rating | 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HT (approx. 50 W) @ 125/250 VAC for inductive loads |
Relay operation | automatic (non-latching); latching (requires manual acknowledge); sampling (based on time); pump alteration control (2 to 8 relays); Off (disable unused relays and enable interlock feature, manual on/off control mode) |
Time delay | 0 to 999.9 seconds, on and off relay time delays; programmable & independent for each relay |
Serial communications | |
---|---|
Protocol | Modbus RTU |
Meter address/Slave ID | 1 to 247 |
Baud rate | 300 to 19,200 bps |
Transmit time delay | Programmable between 0 and 199 ms |
Data | 8 bit (1 start bit, 1 or 2 stop bits) |
Parity | Even, odd or none with 1 or 2 stop bits |
Byte-to-byte timeout | 0.01 - 2.54 seconds |
Turn around delay | < 2 ms (fixed) |
Isolated 4-20mA transmitter output | |||
---|---|---|---|
Output source | Process channel A, B, or C, max or min for channel A, B, or highest and lowest max or min of A and B, set points 1-8, Modbus input, or manual control mode |
||
Scaling range | 1.000 to 23.000 mA for any display range | ||
Accuracy | ±0.1% of span ±0.004 mA | ||
Temperature drift | 0 to 65°C ambient: 0.4 μA/°C max -40 to 0°C ambient: 0.8 μA/°C max |
||
Isolated transmitter power supply | Terminals I+ & R: 24 VDC ±10%, isolated from the input at >500 V; may be used to power the 4-20 mA output or other devices; all models rated @ 40 mA max |
||
External loop power supply | 35 VDC maximum | ||
Output loop resistance: | Power supply | Minimum | Maximum |
24 VDC | 10 Ω | 700 Ω | |
35 VDC (external) | 100 Ω | 1200 Ω |
Easy to use, customizable displays
The dual-line display makes the PCD200 easy to set up and program, and all configuration can be done via the front panel. PCD200 series panel meters have an upper and lower display, each a full 6 digits (-999999 to 999999).
The displays can be set up to read input channels (A or B), math function channel C, toggle between A & B, B & C, A & C, A & B & C, toggle between channels A, B, or C & units, the max/min of any of the channels (including math channel C), set points, gross, or net & gross values of channel A or B, or the Modbus input. This allows the meter to show the most relevant variables for the application.
Alternation display
Certain options alternate the display information. A single display can show input variable information as well as that channel’s unit or tag. Input and math function channels, gross and net values, and select inputs and the math results may also alternate on a single display.
Standard LED and SunBright LED display models
PCD200 panel meters feature ultra-bright LED displays. Both standard and SunBright models perform well in both indoor and outdoor settings where visibility may be impaired by smoke, fog, dust, or distance. The UV-resistant SunBright display option is even readable in sunlight and ideal for use in outdoor applications.
Model | Input power | Relays | Output | Display type |
---|---|---|---|---|
PCD200-265-B-N-200 | 85-265 VAC | - | - | Standard |
PCD200-24-B-N-100 | 12-24 VDC | - | - | Standard |
PCD200-265-B-2R-200 | 85-265 VAC | 2 relays | - | Standard |
PCD200-24-B-2R-100 | 12-24 VDC | 2 relays | - | Standard |
PCD200-265-B-420-240 | 85-265 VAC | - | 4-20 mA output | Standard |
PCD200-24-B-420-140 | 12-24 VDC | - | 4-20 mA output | Standard |
PCD200-265-B-4R-200 | 85-265 VAC | 4 relays | - | Standard |
PCD200-24-B-4R-100 | 12-24 VDC | 4 relays | - | Standard |
PCD200-265-B-2R420-240 | 85-265 VAC | 2 relays | 4-20 mA output | Standard |
PCD200-24-B-2R420-140 | 12-24 VDC | 2 relays | 4-20 mA output | Standard |
PCD200-265-B-4R420-240 | 85-265 VAC | 4 relays | 4-20 mA output | Standard |
PCD200-24-B-4R420-140 | 12-24 VDC | 4 relays | 4-20 mA output | Standard |
PCD200-265-SB-N | 85-265 VAC | - | - | SunBright |
PCD200-24-SB-N-100 | 12-24 VDC | - | - | SunBright |
PCD200-265-SB-2R | 85-265 VAC | 2 relays | - | SunBright |
PCD200-24-SB-2R-100 | 12-24 VDC | 2 relays | - | SunBright |
PCD200-265-SB-420 | 85-265 VAC | - | 4-20 mA output | SunBright |
PCD200-24-SB-420-140 | 12-24 VDC | - | 4-20 mA output | SunBright |
PCD200-265-SB-4R-200 | 85-265 VAC | 4 relays | - | SunBright |
PCD200-24-SB-4R-100 | 12-24 VDC | 4 relays | - | SunBright |
PCD200-265-SB-2R420-240 | 85-265 VAC | 2 relays | 4-20 mA output | SunBright |
PCD200-24-SB-2R420-140 | 12-24 VDC | 2 relays | 4-20 mA output | SunBright |
PCD200-265-SB-4R420-240 | 85-265 VAC | 4 relays | 4-20 mA output | SunBright |
PCD200-24-SB-4R420-140 | 12-24 VDC | 4 relays | 4-20 mA output | SunBright |