Phone: +1-301-330-88111-800-WILCOXON
Intrinsically safe vibration transmitter, 4-20 mA output proportional to peak velocity vibration, 3.0 in/sec full-scale measurement range, ±5% tolerance at full scale, operates up to 85°C, top exit 2-pin MIL-C-5015 style connector, certified for use in Class I Division 1 and Zone 0 / Zone 1 hazardous locations
PARAMETER | VALUE |
---|---|
Sensor output | 4-20 mA |
Measurement unit | Velocity |
Detector type | Peak |
Full-scale range | 3 IPS |
Frequency response, ±3dB | 4 Hz - 2,000 Hz |
Connector style | MIL-C-5015, 2-pin |
Connector orientation | Top exit |
Temperature range | -40°C to +85°C |
Weight | 162 grams |
Hazardous area approvals | Class I, Div 1; ATEX II 1G Ex ia; IECEx Ga Ex ia |